Parameters of Air Cooled Mini Chiller 

Air Cooled Mini Chiller
Parameters Type HWAC 03/D HWAC 05/D HWAC 05 HWAC 06 HWAC 08 HWAC 10 HWAC 12 HWAC 15
HWAC 03H/D HWAC 05H/D HWAC 05H HWAC 06H HWAC 08H HWAC 10H HWAC 12H HWAC 15H
Cooling Capacity KW 7.1 13 13.3 16 21.8 26 32 39
Heating Capacity KW 7.2 13.5 13.8 16.5 23 27.5 34 41.5
Heating Capacity of Heat Recovery KW 5 10 10 12 16 22 25 31
Power supply 220V/1PH-50HZ 380V/3PH-50HZ
Cooling Power Input KW 2.9 4.2 4.28 5.4 7 9.8 12.8 14.5
Heating Power Input KW 3 4.25 4.3 5.5 7.1 10 13.6 15
Protection Devices high and low pressure protection, anti-frozen protection, over load protection, phase order protection, over-heat protection of compressor
Operation Equipment microcomputer control automatically, failure warning
Switch Device for Cooling/Heating four-way directional control valve
Compressor Type hermetic rotary compressor hermetic scroll compressor
Power KW 2.23 2.23×2 3.75 4.5 3.75+2.23 3.75×2 4.5×2 3.75×3
Air Side Heat Exchanger Type copper tube with aluminum fin
Fan Type ultra-low noise axial type
Air Blowing Direction vertical side blowing/horizontal vertical side blowing/vertical top blowing/horizontal
Air Flow m3/h 4000 6200 6200 6800 8000 11000 12500 15000
Fan Power KW 0.1 0.25 0.25 0.37 0.1×2 0.25×2 0.37×2 0.5×2
Water Side Heat Exchanger Type stainless steel plate/high efficiency shell and tube
Water Resistance kpa 30 35 35 39 42 45 45 46
Connecting Pipe in 1" 1" 1" 1" 1      
Water Pump Water Flow m3/h 1.6 2.8 2.8 3.5 4 4.8 6.2 8.2
External Pressure Head m 22 22 22 22 22 20 20 20
Rated Power KW 0.55 0.55 0.55 0.55 0.75 0.75 1.1 1.5
Refrigerant R22/R407C
Internal Expansion Water Tank L 5 8
Operation Noise Level dB(A) 56 58 58 58 60 61 61 63
Net Weight kg 136 130 156 200 260 300 360 580
Unit Dimensions Length mm 800 800 1000 1200 1600 1600 1600 1800
Width mm 500 500 550 550 800 800 800 1000
Height mm 1200 1200 1600 1600 1600 1600 1700 1700

Note: 1. "H" means heat pump type, "D" means single phase power supply.
2. Nominal cooling condition: outside air temperature DB35℃/WB24℃, chilled water temperature 12/7℃.
3. Nominal heating condition: outside air temperature DB7℃/WB6℃, chilled water temperature 40/45℃.
4. The units contain water pump and expansion tank.
5. Owing to technological advances, the above specifications are subject to change without notice.
6. If any other special specifications are needed, please notify us in advance.