Parameters of Ducted Split Type Air Conditioner
Model | HA D 03 (H) |
HA D 05 (H) |
HA D 06 (H) |
HA D 08 (H) |
HA D 10 (H) |
HA D 12 (H) |
HA D 15 (H) |
HA D 18 (H) |
HA D 20 (H) |
HA D 25 (H) |
HA D 30 (H) |
HA D 36 (H) |
HA D 40 (H) |
HA D 50 (H) |
HA D 60 (H) |
|||
Unit perfor- mance | Cooling capacity |
kw | 7.8 | 13 | 15.6 | 20.8 | 26 | 31.2 | 39 | 46.8 | 52 | 65 | 78 | 93.6 | 104 | 130 | 156 | |
Heating capacity |
kw | 8.1 | 13.6 | 16.5 | 22.1 | 27.5 | 33 | 41.5 | 50.2 | 56.8 | 69 | 82 | 98 | 110 | 136 | 162 | ||
Electric heating |
kw | 3 | 4 | 5 | 6 | 8 | 9 | 12 | 15 | 16 | 18 | 25 | 30 | 32 | 36 | 50 | ||
Air flow | m3 /h |
17 00 | 26 00 | 31 00 | 41 00 | 54 00 | 65 00 | 80 00 | 96 00 | 108 00 | 138 00 | 160 00 | 195 00 | 205 00 | 255 00 | 270 00 | ||
External static pressure | Pa | 80 | 100 | 110 | 110 | 120 | 180 | 200 | 200 | 220 | 230 | 230 | 260 | 300 | 340 | 350 | ||
Power Supply | 220V | 380V/3N~50Hz | ||||||||||||||||
Refri- gerant | Type | R22/R407C | ||||||||||||||||
Volume control |
capillary tube/expansion valve | |||||||||||||||||
Charge | kg | 3.5 | 5 | 5 | 5+ 3.5 | 5 ×2 | 5.6 ×2 | 5×3 | 5.6 ×3 | 5×4 | 5.6 ×4 | 10×2 +5 | 10 ×3 | 10× 2 + 5 |
10× 4 |
10× 5 |
||
Comp- ressor | Type | flexible hermetic scroll compressor | ||||||||||||||||
Power | kw | 2.25 | 3.75 | 4.5 | 3.75 +2.25 | 3.75 ×2 | 4.5 ×2 | 3.75 ×3 | 4.5 ×3 | 3.75 ×4 | 4.5 ×4 | 9× 2 + 3.75 |
9× 3 |
9× 3 + 3.75 |
9× 4 |
9× 5 |
||
Eva- porator | Type | copper tube with aluminum fin | ||||||||||||||||
Fin type | Slotted-type two-way aluminum fin/honeycomb type aluminum fin | |||||||||||||||||
Indoor unit | Fan | Type | centrifugal type | |||||||||||||||
Driving method |
direct-drive | belt-drive | ||||||||||||||||
Power | kw | 0.25 | 0.55 | 0.55 | 0.28 *2 | 0.55 *2 | 1.5 | 2.2 | 2.2 | 3 | 3 | 4 | 5.5 | 5.5 | 7.5 | 11 | ||
Unit Dime- nsion | L | mm | 80 0 | 10 00 | 11 00 | 12 50 | 12 50 | 14 50 | 16 50 | 17 20 | 18 00 | 18 00 | 2000 | 21 00 |
22 00 |
24 00 |
25 50 |
|
W | mm | 500 | 500 | 500 | 600 | 600 | 800 | 800 | 800 | 800 | 900 | 900 | 10 00 |
10 00 |
13 00 |
15 00 |
||
H | mm | 14 00 | 15 00 | 15 00 | 16 00 | 1600 | 1700 | 1800 | 1950 | 1950 | 2000 | 2000 | 22 00 |
22 00 |
22 50 |
24 00 |
||
Weight | kg | 70 | 90 | 100 | 140 | 160 | 225 | 280 | 320 | 350 | 440 | 480 | 580 | 630 | 700 | 815 | ||
Noise level | dB/ (A) |
<50 | <52 | <52 | <52 | <56 | <60 | <65 | <65 | <67 | <67 | <67 | <67 | <68 | <70 | <72 | ||
Outdoor unit | Comp- ressor | Type | Hermetic Scroll | |||||||||||||||
Power | kw | 2.25 | 3.75 | 4.5 | 3.75 +2.25 | 3.75 ×2 | 4.5 ×2 | 3.75 ×3 | 4.5 ×3 | 3.75 ×4 | 4.5 ×4 | 9×2 +3.75 | 9× 3 |
9× 3 + 3.75 |
9× 4 |
9× 5 |
||
Cond- enser | Type | tube with fin | ||||||||||||||||
Fin type | Slotted-type two-way aluminum fin | |||||||||||||||||
Blower | Type | ultra-low noise axial type | ||||||||||||||||
Driving method |
direct-drive | |||||||||||||||||
Power | kw | 0.18 | 0.25 | 0.25 | 0.55 | 0.71 | 0.75 | 1.1 | 0.71 ×2 | 0.71 ×2 | 0.75 ×2 | 1.1 ×2 | 1.5 ×2 | 0.75 ×3 | 1.1 ×3 | 1.1 ×4 | ||
Unit Dime- nsion | L | mm | 860 | 970 | 840 | 940 | 10 50 | 13 50 | 13 50 | 18 50 | 19 50 | 24 00 | 24 50 | 23 00 |
2800 | 30 00 |
30 00 |
|
W | mm | 300 | 350 | 840 | 940 | 10 50 | 10 50 | 12 00 | 10 50 | 10 50 | 10 50 | 1 100 | 11 00 |
1100 | 11 00 |
11 00 |
||
H | mm | 830 | 12 50 | 950 | 12 50 | 13 00 | 13 00 | 13 00 | 11 50 | 11 50 | 12 50 | 14 00 | 14 00 |
1500 | 15 00 |
16 00 |
||
Weight | kg | 100 | 130 | 140 | 210 | 240 | 360 | 380 | 450 | 480 | 650 | 750 | 860 | 920 | 13 60 |
14 50 |
||
Noise level | dB(A) | 62 | 63 | 63 | 67 | 68 | 69 | 70 | 71 | 71 | 72 | 74 | 75 | 76 | 77 | 78 | ||
Conn- ecting tubes | Refri- gerant gas tube | Size | Ф 15.9 | Ф 19.1 | Ф 19.1 | Ф19 .1 + Ф15. 9 |
Ф 19.1 | Ф 19.1 | Ф 19.1 | Ф 19.1 | Ф 19.1 | Ф 19.1 | Ф 28 ×2 + Ф 19.1 |
Ф 28 |
Ф 28 ×3 + Ф 19.1 | Ф 28 |
Ф 28 |
|
Quantity | 1 | 1 | 1 | 1 | 2 | 2 | 3 | 3 | 4 | 4 | 1 | 3 | 1 | 4 | 5 | |||
Refri- gerant liquid tube | Size | Ф 9.52 | Ф 12.7 | Ф 12.7 | Ф 12.7 + Ф 9.52 | Ф 12.7 | Ф 12.7 | Ф 12.7 | Ф 12.7 | Ф 12.7 | Ф 12.7 | Ф 15.9 × 2+ Ф 12.7 | Ф 15.9 | Ф 15.9 ×3 + Ф 12.7 | Ф 15.9 | Ф 15.9 | ||
Quantity | 1 | 1 | 1 | 1 | 2 | 2 | 3 | 3 | 4 | 4 | 1 | 3 | 1 | 4 | 5 | |||
Connection method | flare opening | welding+flare opening |
1. Cooling capacity is based on the following conditions: indoor air temperature DB27℃/WB19℃, ambient temperature, 35℃ DB/24℃ WB.
2. Heating capacity is measured when indoor air temperature is 21 ℃, outside air temperature is DB7℃/WB6℃
3. Electric heating capacity refers to cooling and electric heating type unit
4. The specifications are subject to change without notice for improvement.